deplete to before charging starts. Press the Top Right
Key.
g.
And
last, the "Charge Timeout" is "0.00 Hours." Press
the Top Right Key to take you back to “Charge Step
#”.
This first charge step is kind of a placeholder where
nothing really happens to the batteries until their voltage
falls off and they truly do need a charge. That is, the
inverter charges the batteries at 0 Adc until the battery
voltage falls below 22.0 Vdc (
44 V
DC
for the RE48-4500
)
and then goes on to the next charging stage.
2.
Perform the second set of charging steps:
a.
Set "Charge Step #" to 2. (The second charging stage)
Press the Top Right Key.
b.
The "Charge Stage " is "BLKC" standing for bulk
charge current. Press the Top Right Key.
c.
The "Charge Type" is "DC CURRENT." Press the Top
Right Key.
d.
The "Charge Setting" is "100.0 Adc." (+100.0) (
50
A
DC
for the RE48-4500
) Press the Top Right Key.
e.
The "Trigger Type" is ">=DC VOLTAGE." Press the
Top Right Key.
f.
The "Trigger Settng" is "28.40 Vdc." (
56.8 V
DC
for the
RE48-4500
) Press the Top Right Key.
g.
And last, the "Charge Timeout" is "24.00 Hours."
Press the Top Right Key to take you back to “Charge
Step #”.
During this second charging stage, the inverter/charger
will provide 100 Adc into the batteries. The Inverter will
continue to do this until the battery’s voltage has risen to
28.40 Vdc, or until 24 hours have gone by and then the
inverter goes to the next charging stage.
3.
Perform the third set of charging steps:
a.
Set "Charge Step #" to 3. (The third charging stage)
Press the Top Right Key.
b.
The "Charge Stage " is "BLKV" standing for bulk
charge voltage. Press the Top Right Key.
c.
The
"Charge Type" is "DC VOLTAGE." Press the
Top Right Key.