Installation And Start-Up
3-25
Copyright
2001 Phone: (614) 771-2718 RE-4500
Vanner Inc. FAX: 614-771-4904 Owners Manual
4282 Reynolds Dr. www.vanner.com Rev 01e
Hilliard Ohio 43026 RE-Installation_Manual_Rev01e 910157-A
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
17.
Verify that the inverter will turn ON but do not leave the
inverter connected to the DC source(s) at this time (turn off
the DC disconnect). Final DC connections will be made
after all control and AC output installation issues have
been inspected.
AC Utility/Load Wiring
Installation Procedure
Warning
Before proceeding with the AC wiring, verify that the inverter is
OFF and that the inverter is NOT connected to the battery. Serious
or fatal electrical shock may occur.
Please refer to Figure 3-9 if the RE-ACM is not used in this
installation. Please refer to Figure 3-6 for the location of the
AC Raceway. Please refer to Figure 3-10 for location of the
AC Raceway and terminations.
It is recommended by Vanner that you use an AC Control
Module which will take care of the majority of NEC code
requirements for the AC disconnects and terminations.
Note:
It is required that all AC wiring be done with 10 AWG 90ºC wire.
Make certain that the wiring conforms to National and Local
Electric Codes.